Your existing radiators can work with a heat pump. The test is whether each one still covers the heat its room loses, once the water inside it is cooler. A radiator rated at 2,000 watts on a boiler gives only 600 watts at heat pump temperatures. That figure comes from the installation code of practice published on seai.ie. SEAI’s own technology guide says standard steel radiators used with heat pumps “must have around three to seven times the output of a traditional boiler system”. The answer is worked out room by room, from a heat loss calculation, before anything is fitted.
- The water runs cooler. A standard boiler sends water out at about 75°C and gets it back at 65°C. The code of practice aims heat pumps at 45°C out and 40°C back.
- The same radiator gives far less heat. 2,000 watts at boiler temperatures becomes 850 watts at 55°C/45°C. At 45°C/40°C it is 600 watts.
- It is decided room by room. Existing radiators may be kept only in certain cases. Each one is judged against a heat loss calculation for its own room.
- The grant pays where the design calls for it. SEAI offers up to €2,000 towards “new radiators or underfloor heating”. Whether you qualify “will depend on your Contractors installation design”.
Why the Same Radiator Delivers Less Heat
A radiator’s output depends on how much hotter its water is than the room. SEAI’s technology guide calls radiators and underfloor heating “heat emitters”, and sets out the rule: “The output of heat emitters depends on their mean water temperature. When the water temperature is lower, the heat emitter system produces less heat”.
The code of practice on seai.ie sets out the sum behind that. Average the flow temperature, the water going out to the radiators, and the return temperature coming back. Then subtract the room temperature. A standard boiler runs 75°C out and 65°C back, so in a 20°C room that leaves 50°C. A condensing boiler at 65°C/55°C leaves 40°C. A heat pump at 45°C/40°C leaves 22.5°C. And “the higher the ΔT value, the higher the radiator output will be”, as the code of practice puts it. A heat pump works at the bottom of that range.
| Heat source | Flow / return | Temperature difference | Output of a radiator rated 2,000W |
|---|---|---|---|
| Standard efficiency boiler | 75°C / 65°C | 50°C | 2,000W (the rated figure) |
| Heat pump, higher setting | 55°C / 45°C | 30°C | 850W (factor 0.424) |
| Heat pump, efficient setting | 45°C / 40°C | 22.5°C | 600W (factor 0.3) |
Sources: Heat Pumps Code of Practice, Installation Guidelines version 6.0 and SEAI Heat Pumps Technology Guide, both on seai.ie. The worked example uses a radiator giving 2,000 watts at a temperature difference of 50°C.
Radiator makers publish their outputs at the boiler figure of 50°C. So the number on a brochure is not the number a heat pump will get out of it. Those stated outputs, the code of practice says, “must be multiplied by a conversion factor to account for the different ΔT value”. It adds that “manufacturers should be asked to provide conversion factors for different ΔT values”. The 0.424 and the 0.3 above are two of those multipliers.
What Decides Whether Yours Stay
Your installer is working to a standard here. The code of practice requires that “the heat losses of the building must be 100% covered by the heat emitters”. They have to be designed and installed to the current NSAI SR50-1 standard, which covers heat and ventilation losses. So the radiators and underfloor heating have to replace every watt the house loses, with cooler water in the pipes. That is judged at the indoor and outdoor temperatures the designer picks.
Keeping what you have is allowed, but it is not assumed. Where a heat pump goes into a house that is already built, the code of practice says the existing pipes, radiators or hot water cylinder “may be reused” only “under certain circumstances”. This “is to be assessed based on provided heat loss calculations on a room by room basis”. The first test it names is the plain one. Can the existing radiator still meet that room’s heat load at the heat pump’s lower flow temperature, using the maker’s correction factors?
That is a verdict per room, not one verdict on the house. One room may keep its radiator and the room beside it may not. The answer turns on what that radiator can give against what that room loses.
Where a bigger radiator is needed, SEAI’s guide lists the ways to get there. You can increase “the length or height of a radiator”, add panels to it, or add fins. Height and length are the ones you notice. A longer radiator needs wall to sit on. Check that against the room before you sign, rather than on the day of the install.
Steel, Aluminium or Fan-Assisted
Standard steel panel radiators work with a heat pump, as long as they are sized for the lower temperature. SEAI’s guide also notes that “there are radiator types designed for higher heat output at low temperatures”. That is where the alternatives come in.
Aluminium radiators “provide better conductivity, and therefore higher heat output per area, than traditional steel radiators”, the guide says. So they can be more compact. The trade-off sits in the same passage: they are “usually more expensive”. Where wall space is the problem in a room, that cost may buy the only answer that works.
Some radiators come with a fan in them. The guide splits them into passive and active. Passive ones “circulate air by free convection and are usually used in domestic properties”. Active ones “force air flow by using fans”. The fan-assisted kind are either wall-mounted or set in a trench around the edge of a room. The guide says the trench version suits heating under big areas of glass. A fan is a thing to live with in a bedroom, so ask where they are going.
Radiators or Underfloor Heating
Underfloor heating suits a heat pump because it works cooler. SEAI’s guide says underfloor systems in solid floors “usually have a maximum flow temperature of around 50 °C, making them suitable for use with heat pumps”. The code of practice goes further on efficiency. Underfloor heating running up to 35°C gives better seasonal efficiency than fan coil or low temperature radiators running up to 45°C.
The same passage gives up something in return. It says an underfloor system does not match a low temperature radiator system for control and responsiveness. A floor takes longer to react than a radiator does.
Upstairs is where this usually falls down. SEAI’s guide says underfloor systems in suspended timber floors “are often designed to run at up to 70 °C”. So “it is likely that an existing system will have to be altered in order to be served by a heat pump”. Their heat output “is lower than that of solid floors”, so extra heat from another type of heater may be needed. Pipe spacing can also be limited by the joists.
The floor covering decides part of it too. The guide says “the more insulating the floor covering, the lower the output of the underfloor heating”. That is why suppliers put a limit on how insulating your carpet, and the underlay beneath it, can be. In a new system, closer pipe spacing lets the flow temperature drop. That lifts efficiency, at the cost of more pipework.
The Pipework and the Pump Move With Them
Changing radiators is rarely the whole job. The pipework, meaning the pipes that carry the water around the house, can have to change with them. A heat pump works across a smaller temperature difference, so it needs more water moving to deliver the same heat. SEAI’s guide is direct about the result: “it is important that (some or all of) the pipework diameter is large enough, and that the circulation pumps have enough capacity”. It adds that this holds “for new systems, and for retrofitting a heat pump to an existing property”.
Old pipework is a harder question. “Reusing the pipework is not recommended”, the code of practice says. It was built for gas or oil boilers running higher flow temperatures and flow rates, which are “not suitable for low temperature heat pump systems”.
A cheaper option exists. SEAI’s guide describes splitting one circuit into several, which lets the system run at a lower temperature difference, and says that is “much cheaper than upgrading all the pipework”. The guide also recommends a pressure test and a power flush, to work out what needs repair or replacement. On a house with decades-old heating, that is a fair thing to see on a quote.
How the Heating Behaves at Lower Temperatures
New radiators change how the house heats, not just what it costs. With output temperatures between 35°C and 55°C, the code of practice says, “the response time of the heating system is long”. Heat pump systems are “designed to maintain a stable temperature rather than be able to raise the temperature quickly immediately before occupation”. Night setback is possible, but only “with a setback of 2°C to 4°C”.
So the system holds a temperature. It is not fired in short bursts before the house fills up. That is also why the sizing has to be right. The code of practice says the majority of heat pumps have an operating temperature limit of 50°C to 55°C in most applications. There is no option of turning the water up to rescue radiators that are too small.
Where the SEAI Grant Fits
SEAI funds this work inside the heat pump grant bundle. Its grant page lists “Up to €2,000 for upgrade works, where required, to Central Heating components i.e. new radiators or underfloor heating”. The same bundle covers the heat pump itself, and a boiler scrappage grant, paid where an old oil or gas boiler, a solid fuel system or electric storage heating is taken out.
Read the condition on it twice. SEAI says eligibility for the central heating grant “will depend on your Contractors installation design”. The design decides whether the radiator work is required, and that decides whether the €2,000 is there for you. Full amounts sit on our heat pump grant page. What the finished job tends to cost is on heat pump cost Ireland. SEAI also expects “a sufficiently low level of heat loss” before you apply, which our heat loss indicator page covers.
Pricing solar at the same time?
A heat pump runs on electricity, so it changes what solar is worth on your roof. Get a Solar Quote to see what a system would cost.
What to Ask Before You Sign
- Can I see the room by room heat loss calculation? It is where the radiator decision comes from.
- What design flow temperature is this quote based on? 45°C and 55°C give the same radiator very different outputs.
- Which radiators are staying? Ask which correction factor was applied to each of those.
- Where will the bigger radiators go? Extra output can arrive as extra length or height.
- Is any pipework or pump work priced in? A smaller temperature difference needs a higher flow rate.
Frequently Asked Questions
Do I need new radiators for a heat pump in Ireland?
Not always, and not always all of them. The code of practice on seai.ie says existing heat emitters may be reused “only under certain circumstances”. It is assessed from heat loss calculations, room by room. The first test is whether the existing radiator still meets that room’s heat load at the heat pump’s lower water temperature. SEAI’s technology guide says standard steel radiators used with heat pumps must have around three to seven times the output of a traditional boiler system.
How much output does a radiator lose at heat pump temperatures?
The worked example in the code of practice starts with a radiator giving 2,000 watts at a temperature difference of 50°C. The same radiator delivers 850 watts at a 30°C difference, which is flow 55°C and return 45°C. At a 22.5°C difference, flow 45°C and return 40°C, it gives 600 watts. The correction factors used are 0.424 and 0.3.
Is underfloor heating better than radiators with a heat pump?
It is more efficient and less responsive. The code of practice says underfloor heating working up to 35°C gives higher seasonal efficiency than fan coil or low temperature radiator systems working up to 45°C. It also says its control and responsiveness are not at the same level. SEAI’s technology guide adds that underfloor heating in solid floors usually has a maximum flow temperature of around 50°C, which suits a heat pump. Systems in suspended timber floors are often designed to run at up to 70°C, and are likely to need alteration.
Does the SEAI grant pay for new radiators?
Up to €2,000, where the works are required. SEAI’s heat pump grant page offers “Up to €2,000 for upgrade works, where required, to Central Heating components i.e. new radiators or underfloor heating”. It also states that eligibility for the central heating grant “will depend on your Contractors installation design”.
Can I keep my existing pipework?
The code of practice on seai.ie says reusing it “is not recommended”. Existing pipework was designed for gas or oil boiler systems, at higher flow temperatures and flow rates. Those are not suitable for low temperature heat pump systems. SEAI’s technology guide says the width of the pipes and the capacity of the circulation pump both have to be sufficient, in a new system and in a house that already exists.
Written by Neil Russell · Figures verified against SEAI’s Heat Pumps Technology Guide, the Heat Pumps Code of Practice on seai.ie and the SEAI heat pump grant page.